The Right Replacement Fill for Your Cooling Tower – FM Industry
* Note: “Selection Program GPM” is a calculated prediction of how many gpm of water a Series 3000 unit with the original fill could cool with a given air inlet temperature, water inlet and outlet temperatures, and power consumption. The “Selection Program GPM” in this table above states that each of CT-1 and CT-2 with the original fill has the thermal capacity to cool 2799 gallons of water per minute from Entering Water Temp (F°) 82.1 91.2 91.4 82°F to 73°F at 60°F wet bulb while consuming 35 kW of power. Each of these same towers with the original fill can also cool 1984 gallons of water per minute from 82° to 71°F at 61°F wet bulb while consuming 36 kW of power.
Steve Kline, P.E., MBA, is Product Applications Manager at Baltimore Aircoil Company, Inc., which specialises in cooling towers, closed circuit cooling, evaporative condensers and ice thermal storage solutions.